来源:中国制冷配件网 添加人:chinazlsxy 添加时间:2005-7-14 14:45:14

Type Application Problem Ceiling Height (feet) Air Change Rate Per hour Recommended Amount Outside Air Remarks Minimum Air
Filler Efficiency
ASHRAE Std. 52
Recommended Minimum
Airline Reservaion
Centers and
Telecommunications
Centers
Tobacco Smoke
 
 
 
8-10
12-14
16-18
 
15
12
10
 
12
10
8
 
10%
10%
10%
 
 
 
 
 
55%
55%
55%
 
Airport Terminals
 
 
 
Jet, Truck, Bus
and Auto Fumes
Tobacco Smoke
Food Odors
8-10
12-14
16-18
 
10
8
7
 
9
7
7
 
10%
10%
10%
 
 
 
 
 
80%
80%
80%
 
Animal Laboratories
 
Animal and
Medical Odors
8-10
12-14
25
20
23
18
25%
25%
Air Distribution
Important Consideration
95%DOP
 
Bingo Halls and
Casinos
 
Tobacco Smoke
and Odor
 
8-10
12-14
16-18
17
15
13
16
14
12
10%
10%
10%
1 Person/20 Sq. Ft.
1 Person/25 Sq. Ft.
1 Person/30 Sq. Ft.
55%
55%
55%
Bowling Centers
 
 
Tobacco Smoke
Beer and Perspiration
Odors
10-12
 
 
10
 
 
8.5
 
 
10%
 
 
 
 
 
55%
 
 
Computer Rooms
 
 
Outside air contami-
nants; computer qener-
ated dust and qases
8-10
 
 
20
 
 
18
 
 
Minimun
 
 
Under Floor, Through
Cabinet Air Distribution
 
40-55%
 
 
Conference and
Meeting Rooms
 
Tobacco Smoke
and Odor
 
8-10
12-14
16-18
15
12
10
13
10
10
10%
10%
10%
 
 
 
55%
55%
55%
Convention Centers
and Sports Arenas
 
 
 
Heavy Tobacco
Smoke and Animal
Odors
 
 
30-40
40-50
50-60
60-80
80-100
8
7
6
5
4
7
6
5
4
4
5 CFM/Person
5 CFM/Person
5 CFM/Person
5 CFM/Person
5 CFM/Person
 
 
 
 
 
55%
55%
55%
55%
55%
Data Processing
Centers
Dust and Dirt
Deposition
8-12
 
30
 
25
 
10%
 
Under Floor Air Distribution
High Speed Printers
80%
 
Department Stores
 
Dust, Dirt and
Food Odors
10-15
 
10
 
8
 
10%
 
 
 
80%
 
Graphic Aris
Industry
 
Soivent Odors
Dust and Dirt
Deposition
8-10
10-12
12-15
20
18
16
18
16
14
10%
10%
10%
Or Amount to Balance
Exhaust Air
 
80%
80%
80%
Hospital Operating
Suites
Medical Odors
 
10-12
 
25
 
25
 
25%
 
In Accordance with
USPHS Recommendations
95%DOP
 
Laboratories
 
Chemical Odors, Dust
and Dirt Deposition
8-10
12-14
20
18
18
16
15%
15%
Outside Air to Balance
Exhaust Air Hoods
80%
 
Libraries and
Museums
Dust and Dirt
Deposition
10-12
14-16
12
10
10
8
10%
10%
 
 
90%
 
Magnetic Tape or
Film Manufacturing
and Processing
Chemical Odors
 
 
10-12
14-16
 
18
16
 
16
15
 
15%
15%
 
 
 
 
90%
90%
 
Nursing and Special
Care Institutions
Medical and Human
Waste Odors
8-10
 
15
 
13
 
10%
 
 
 
90%
 
Office Buildings
 
 
 
Tobacco Smoke
and Odor
 
 
8-10
 
 
 
10
7.5
5
4.5
8.5
6
4.5
4
10%
10%
10%
10%
1 Person/30 Sq.Ft.
1 Person/50 Sq.Ft.
1 Person/75 Sq.Ft.
1 Person/100 Sq.Ft.
55%
55%
55%
55%
Pistol Ranges
 
 
 
Lead Dust
and Fumes
 
 
 
 
 
 
20 min.
 
 
 
 
 
 
 
 
 
 
 
Air Distrlbution is Critical-
50 FPM Face Velocity Down
Range of Shooting Booth
(Minimum Allowed)
45-55%
(Pre-Filter)
85-95%
(Final Filter)
Precision
Manufacturing
Oil and Process
Exhaust Fumes
10-12
14-16
20
18
18
17
15%
15%
 
 
80%
80%
Restaurant Dining
Areas and Lounges
 
Tobacco Smoke
Food Odors
 
8-10
12-14
16-18
15
13
11
13
11
10
10%
10%
10%
1 Person/35 Sq. Ft.
1 Person/50 Sq. Ft.
1 Person/75 Sq. Ft.
55%
55%
55%
 
Grills or Fryers in Open Restaurant Areas Will Increase Air change Rate by 30%
 
Telephone Central
Switching Stations
 
 
Dust and Dirt
Deposition on
Electuical Equopment
 
Step Switch
12-15
Elect.Switch
12-15
 
9
 
18
 
7
 
15
 
10%
 
10%
 
Air Distribution Pattern
Important to all Equipment
 
 
80%
 
80%
Vocational or
Technical Schools
Welding and
Machine Fumes
10-12
14-16
18
16
16
14
15%
15%
 